The APC Smart-UPS® RT is a high-performance, uninterruptible power supply (UPS) that provides protection for electronic equipment from utility power blackouts, brownouts, sags and surges. The UPS filters small utility line fluctuations and isolates electronic equipment from large disturbances by internally disconnecting from utility line power. Read and download APC Smart UPS 1500 VA User's Manual Online. Download free APC user manuals, owners manuals, instructions, warranties and installation guides, etc.

Files for
  • #
    28.07.2015458.4 Kb5User Manual 2.pdf
Size:Download

English

APC Smart-UPS

1500/3000 VA 120/230 Vac

Modular

Uninterruptible Power Supply

990-170401/2004

Introduction

This APC Smart-UPSis a modular Uninterruptible Power Supply (UPS) for high availability applications such as data centers and mission critical processes, designed to prevent blackouts, brownouts, sags, and surges from reaching your equipment. The UPS filters small utility line fluctuations and isolates your equipment from large disturbances by internally disconnecting from the utility line. The UPS provides continuous power from its internal battery until the utility line returns to safe levels or the battery is fully discharged.

1: INSTALLATION

The User Manual and Safety Guide are accessible on the supplied User Manuals CD and on the APC web site, www.apc.com.

Unpack

Attention: Read the safety instruction sheet before installation.

Inspect the UPS upon receipt. Notify the carrier and dealer if there is damage. The packaging is recyclable; save it for reuse or dispose of it properly. Check the package contents:

UPS

Bezel

Tower conversion top panels and mounting stabilizers

Rail kit

UPS literature kit containing:

Product documentation, safety,

Serial and USB communication

and warranty information

cables

Smart-UPSUser Manuals CD

230 V models only:

PowerChute® CD

Two input power cords

Network Management Card CD

Four output jumper cords

Mounting hardware

Position the UPS in the Specified Environment

0-40°C

0-95%

1

Mount the UPS in the Rack and Connect the Battery

Attention: Install the rails following the instructions in the rail kit.

Rear

2

Tower Configuration

Press and hold the black switch (see location

designation on UPS) to the right while removing the power processing module.

Snap the display bezel out the rear to begin rotation.

Note: Place the UPS in the final operating location prior to module reinstallation.

Rear

3

2: START UP

Connect Equipment to the UPS

Rear Panels

1500 VA, 120 V:

1500 VA, 230 V:

3000 VA, 120 V:

3000 VA, 230 V:

Note:

The ‘outlet groups’ can be controlled through the network software. See Network Management Card documentation.

A laser printer draws significantly more power than other types of equipment and may overload the UPS.

Connect the UPS to the Network (if Applicable)

Network Connectors

Serial Port

USB Port

Ethernet Port

Note:

Use only the supplied cable to connect to the Serial Port. A standard serial interface cable is incompatible with the UPS. Serial and USB ports cannot be used simultaneously.

If an optional Smart-Slotaccessory is to be used, remove the preinstalled network management card and install it now.

Start the UPS

Attention: Upon utility power connection, the UPS will automatically turn on.

1.Plug the UPS into a two-pole,three-wire,grounded receptacle only. Input Plugs:

1500 VA models: 120 V = NEMA5-15P;230 V = Use country specific 10 A with C14 input cords (not supplied).

3000 VA models: 120 V = NEMAL5-30P;230 V = Use the supplied cords or the country specific equivalent.

4

The battery will charge to full capacity during the first few hours of normal operation. Do not expect full ‘on battery’ capability during this initial charge period.

2.After the UPS has ended the immediate self-testwithonline LED illumination, check the front display for any fault indicators (seeTroubleshooting).

3.120 V models: Check thesite wiring fault LED located on the rear panel. It will be illuminated if the UPS is plugged into an improperly wired utility power outlet (seeTroubleshooting).

4.Turn on all connected equipment. To use the UPS as a master on/off switch, be sure all connected equipment is on.

Equipment is now powered and protected. Basic operation, user configuration, and software utilization can now be performed as required.

Apc Smart Ups 3000 Support

Battery Operation

The UPS switches to battery operation automatically if the utility power fails. While running on battery, an alarm beeps four times every 30 seconds. Press the button to silence this alarm.

If the utility power does not return, the UPS continues to supply power to the connected equipment until the battery is fully discharged.

Refer to www.apc.com for battery runtime charts.

When the UPS reaches the low battery shutdown warning (two minute default), the alarm will beep continuously until total shutdown. Connected equipment should be shut down during this time, unless being controlled by network monitoring software.

Apc Smart Ups 3000 Service Manual Pdf

5

3:BASICOPERATION

Front Display Panel

INDICATOR

DESCRIPTION

Online

The UPS is supplying utility power to the connected equipment.

AVR

The UPS is compensating for either a high or low utility voltage.

On Battery

The UPS is supplying battery power to the connected equipment.

Overload

The connected loads are drawing more than the UPS power rating.

Bypass

The connected loads are being powered directly by the utility power connection

and not through the power processing module. This is a fault condition, which

may be caused by an overload or a failure within the module (see Troubleshoot-

ing).

Replace Battery/

The battery is disconnected or must be replaced.

Battery Disconnected

FEATURE

FUNCTION

Power Off

Press this button to turn off the UPS.

6

FEATURE

FUNCTION

Self-Test

Automatic: The UPS performs aself-testautomatically when turned on, and

every two weeks thereafter (by default). During the self-test,the UPS briefly

operates the connected equipment on battery.

Manual: Press and hold the

button for a few seconds to initiate the self-

test.

Cold Start

Supply battery power to the UPS and connected equipment in the absence of

utility voltage (see Troubleshooting). Press the

button for one second and

release. The UPS will beep briefly and go quiet. Press and hold the button again,

but for approximately three seconds. The unit will emit a sustained beep. Re-

lease the button during this beep.

Diagnostic Utility

The UPS has a diagnostic feature that displays the utility voltage.

Voltage

The UPS starts a self-testas part of this procedure. Theself-testdoes not

affect the voltage display.

Press and hold the

button to view the utility voltage bar graph display.

Hip hop beat maker software. We will post the new test results and reviews when we next test Music Production Software. It is expensive compared with some of the production programs we tested, but it has features similar to software that costs three times as much. The virtual instrument library is one of the best available and can be used for live performances as well as in the studio.Logic’s virtual drum plug-in uses an AI algorithm to adapt a virtual drummer to the style of music you produce. Expensive compared with other programs we reviewedIf you have a Mac and want to record, produce and edit audio, Logic is the best program available. It is common practice to start a song with a drumbeat, but with the Logic drummer track plug-in you can record a melody first.

After a few seconds, this five-LEDbattery charge

display on the right of

the front panel will show the utility input voltage.

Refer to the figure at left for the voltage reading (values are not listed on the

UPS).

The display indicates the voltage is between the displayed value on the list and

the next higher value (see Troubleshooting).

7

4:USERCONFIGURABLEITEMS

NOTE: SETTINGS ARE MADE THROUGH THE SUPPLIEDPOWERCHUTE SOFTWARE OR

THE NETWORK INTERFACE CONNECTION. REFER TO THE SOFTWARE HELP GUIDES FOR DETAILS.

FUNCTION

FACTORY

USERSELECTABLE

DESCRIPTION

DEFAULT

CHOICES

Automatic Self-Test

Every 14 days

Every 14 days

This function sets the interval at which the

(336 hours)

(336 hours),

UPS will execute a self-test.

Every 7 days

(168 hours),

On Startup Only,

No Self-Test

UPS ID

UPS_IDEN

Up to eight characters

Use this field to uniquely identify the UPS,

(i.e. server name or location) for network

management purposes.

Date of Last Battery

Manufacture Date

mm/dd/yy

Reset this date when you replace the inter-

Replacement

nal battery module.

Minimum Capacity

0 percent

0, 15, 30, 45, 60, 75, 90

The UPS will charge its batteries to the

Before Return from

percent

specified percentage before powering up

Shutdown

connected equipment, following a low-

battery shutdown.

Voltage Sensitivity

High

High, Medium, Low

The UPS detects and reacts to line voltage

distortions by transferring to battery power

to protect the connected equipment. When

power quality is poor, the UPS may fre-

quently transfer to battery power. If the

connected equipment can operate normally

under such line voltage conditions, reduce

the sensitivity setting to conserve battery’s

capacity and service life.

Alarm Control

Enable

Enable, Mute, Disable

User can mute an ongoing alarm or disable

all existing alarms permanently.

Shutdown Delay

90 seconds

90, 180, 270, 360, 450,

The interval is set between the times when

540, 630, 0 seconds

the UPS receives a shutdown command and

when it shuts off power to the outlets.

Low Battery Warning

2 minutes

2, 5, 8, 11, 14, 17, 20,

PowerChute software provides automatic,

23 minutes

unattended shutdown when the remaining

battery runtime matches this setting while

on battery.

Change the low battery warning interval

default setting to the time that the operating

Heritage of kings the settlers Download The Settlers Game Free For PC Full Version Ghazala Batool December 3, 2018 Adventure The Settlers Game is an adventure video game created by one of the most famous creators which have developed by Blue Byte, published by under the banner of Ubisoft who had made many other installments. Jul 17, 2019  The Settlers is a medieval city building simulation game by Blue Byte Software, first released in 1993 for Commodore Amiga and in 1994 for MS-DOS. In America, it was published as Serf City: Life Is Feudal. It took over two years to code the game to understand supply and demand. Safe Install Game! Irrespective of the reasons, players eagerly await the launch of the next installment as the thrill of a progressive game makes them a vital part of the game as active contributors for the game’s progress. The PC Game, The Settlers is one such video gaming series that follows a legacy of over 25-years where the latest version of the game has an advanced storyline that.

system or system software requires to

safely shut down.

Synchronized Turn-on

0 seconds

0, 60, 120, 180, 240,

The UPS will wait the specified time after

Delay

300, 360, 420 seconds

the return of utility power before turn-on

(to avoid branch circuit overload).

8

Size:Download

English

Smart-UPS®RT

3000/5000/6000 VA 200-240Vac

Tower/Rack Mount 3U

Uninterruptible Power Supply

2009 APC by Schneider Electric. APC, the APC logo, Smart-UPSand PowerChute are owned by Schneider Electric Industries S.A.S., American Power Conversion Corporation, or affiliated companies. All other trademarks are the property of their respective owners.

990-1289E04/2010

Introduction

The APC by Schneider Electric Smart-UPSRT is ahigh-performance,uninterruptible power supply (UPS) that provides protection for electronic equipment from utility power blackouts, brownouts, sags and surges. The UPS filters small utility line fluctuations and isolates electronic equipment from large disturbances by internally disconnecting from utility line power. The UPS provides continuous power from the internal battery until utility power returns to safe levels or the battery is fully discharged.

INSTALLATION

Read the Safety Guide before installing the UPS.

Unpacking

Inspect the UPS upon receipt. Notify the carrier and dealer if there is damage. The packaging is recyclable; save it for reuse or dispose of it properly.

Check the package contents:

UPS (with battery modules disconnected)

Front bezel

Literature kit containing:

Product documentation, Safety Guide, and Warranty Information

Smart-UPSRT User Manuals CD

Software CD

Serial cable

3000 VA XLI models: three output power cords, two input power cords

5000/6000 VA XLI models: six output power cords, Network Management Card documentation

Specifications

TEMPERATURE

This unit is designed for indoor use

OPERATING

32° to 104° F (0° to 40° C)

only. Select a location sturdy enough to

STORAGE

5° to 113° F (-15°to 45° C) charge the UPS

handle the weight.

battery every six months

Do not operate the UPS where there is

MAXIMUM

excessive dust or the temperature and

ELEVATION

humidity are outside the specified limits.

OPERATING

10,000 ft (3,000 m)

Ensure that the air vents on the front

STORAGE

50,000 ft (15,240 m)

and rear of the UPS are not blocked.

HUMIDITY

0 to 95% relative humidity

WEIGHT

UPS

120 lbs (55 kg)

UPS WITH

140 lbs (64 kg)

PACKAGING

.

1

Wiring and Connecting the UPS

5000/6000 VA XLI MODELSONLY: HARDWIRINGINSTRUCTIONS

Wiring must be performed by a qualified electrician.

Install a high magnetic 30/32 A utility circuit breaker.

Adhere to all national and local electrical codes.

Use #10 AWG gauge (5 mm2) wire.

1.Switch the utility circuit breaker OFF.

2.Remove the input access panel.

3.Remove circular knockout.

4.Run #10 AWG gauge (5 mm2) wire through the access panel, and connect the wires to the terminal block (green: ground, brown: hot, blue: neutral). Use an appropriate strain relief (not included).

5.Switch the utility circuit breaker ON.

6.Check line voltages.

7.Replace the access panel.

CONNECTING THEBATTERY MODULES ANDATTACHING THEFRONTBEZEL

.

3

BASICCONNECTORS

Power management software and interface kits can be used with the UPS.

serial com

Use only interface kits supplied or approved by APC.

Any other serial interface cable will be incompatible with the UPS

connector.

Manual bypass enables the user to manually put connected equipment into

bypass mode.

normal bypass

Emergency Power Off terminal allows the user to connect the UPS to the

central EPO system.

EPO terminal

The UPS features a transient voltage surge-suppression(TVSS) screw for

connecting the ground lead on surge suppression devices such as telephone

TVSS screw

and network line protectors.

When connecting grounding cable, disconnect the unit from the utility

power outlet.

Optional external battery packs provide extended runtime during power

outages. These units support up to ten external battery packs.

external battery

See the APC Web site, www.apc.com for the information on the external

pack connector

battery pack, SURT192XLBP.

5000/6000 VA

XLI models

output circuit breakers

3000/5000/6000 VA XLJ/XLT/XLTW models

output circuit breaker

CONNECTINGEQUIPMENT ANDPOWER TO THEUPS

1.Connect equipment to the UPS (cables not included for XLJ/XLT/XLTW models).

2.Avoid using extension cords.

3000 VA XLJ/XLT/XLTW/XLI and 5000/6000 VA XLJ/XLT/XLTW models: Using a power cord, plug the UPS into a two-pole,three-wire, grounded receptacle only.

5000/6000 VA XLJ and 6000 VA XLT models: To draw full power from the UPS have a qualified electrician cut off the input plug and hardwire the UPS to the appropriate power panel.

3.Turn on all connected equipment. To use the UPS as a master ON/OFF switch, ensure all connected equipment is switched ON. The equipment will not be powered until the UPS is turned on.

4.To power up the UPS press the button on the front panel.

The UPS battery charges when it is connected to utility power. The battery charges to 90% capacity during the first three hours of normal operation. Do not expect full battery run capability during this initial charge period.

5.For additional computer system security, install PowerChute® Business Edition Smart-UPSmonitoring software.

OPTIONS

Refer to the APC Web site, www.apc.com for available accessories.

External Battery Pack SURT192XLBP

Rail Kit SURTRK2

Isolation Transformer

Service Bypass Panel

.

5

OPERATION

Load

SMART-UPS RT FRONTDISPLAY

Battery Charge

Indicator

Description

Online

The Online LED illuminates when the UPS is drawing utility power and performing

double conversion to supply power to connected equipment.

On Battery

The UPS is supplying battery power to the connected equipment.

Bypass

The Bypass LED illuminates indicating that the UPS is in bypass mode. Utility

power is sent directly to connected equipment during bypass mode operation.

Bypass mode operation is the result of an internal UPS fault, an overload condition

or a user initiated command either through an accessory or the manual bypass

switch. Battery operation is not available while the UPS is in bypass mode. Refer to

Troubleshooting in this manual.

Fault

The UPS detects an internal fault.

Refer to Troubleshooting in this manual.

Overload

An overload condition exists. See Troubleshooting.

Replace

The battery is disconnected or must be replaced. See Troubleshooting.

Battery

Feature

Function

Power On

Press this button to turn on the UPS. (See below for additional capabilities.)

Power Off

Press this button to turn off the UPS.

Feature

Function

Cold Start

When there is no utility power and the UPS is off, press and hold the

button to

power up the UPS and connected equipment.

The UPS will emit two beeps. During the second beep, release the button.

Self-Test

Automatic: The UPS performs aself-testautomatically when turned on, and every

two weeks thereafter (by default). During the self-test,the UPS briefly operates the

connected equipment on battery.

Manual: Press and hold the

button for a few seconds to initiate the self-test.

Diagnostic Utility Voltage

The UPS has a diagnostic feature that displays the utility voltage. Plug

the UPS into the normal utility power.

The UPS starts a self-testas part of this procedure. Theself-test

does not affect the voltage display.

Press and hold the

button to view the utility voltage bar graph

display. After a few seconds the five-LED,Battery Charge

display

on the right of the front panel shows the utility input voltage.

Refer to the figure at left for the voltage reading (values are not listed

on the UPS).

The display indicates the voltage is between the displayed value on the

list and the next higher value.

Apc Smart Ups 3000 Rackmount

On Battery Operation

Apc Smart Ups 1500 User's Manual

The UPS switches to battery operation automatically if the utility power fails. While running on battery, an alarm beeps four times every 30 seconds.

Press the button to silence this alarm. If the utility power does not return, the UPS continues to supply power to the connected equipment until the battery is fully discharged.

When 2 minutes of run time remain the UPS emits a continuous beeping. If PowerChute is not being used, files must be manually saved and the computer must be turned off before the UPS fully discharges the battery.

The UPS battery life differs based on usage and environment. Refer to www.apc.com, for on battery runtimes.

.

7

USERCONFIGURABLEITEMS

NOTE: SETTINGS ARE MADE THROUGH SUPPLIEDPOWERCHUTE SOFTWARE OPTIONALSMARTSLOT ACCESSORY CARDS ORTERMINALMODE.

FUNCTION

FACTORY

USERSELECTABLE

DESCRIPTION

DEFAULT

CHOICES

Automatic Self-Test

Every 14 days

Every 7 days(168 hours),

Set the interval at which the

(336 hours)

14 days (336 hours)

UPS will execute a self-test.

On Startup Only,

No Self-Test

UPS ID

UPS_IDEN

Up to eight characters to

Uniquely identify the UPS, (i.e.

define the UPS

server name or location) for

network management purposes.

Date of Last Battery

Manufacture Date

Date of

Reset this date when you replace

Replacement

Battery Replacement

the battery modules.

mm/dd/yy

Minimum Capacity

0 percent

0, 15, 25, 35, 50, 60, 75,

Following a low-battery

Before Return from

90 percent

shutdown, the battery modules

Shutdown

will be charged to the specified

percentage before powering

connected equipment.

Alarm Delay After

5 second delay

5 or 30 second delay

Mute ongoing alarms or disable

Line Failure

At Low Battery

all alarms permanently.

Never

Shutdown Delay

20 seconds

0, 20, 60, 120, 240, 480,

Set the interval between the time

720, 960 seconds

when the UPS receives a

shutdown command and the

actual shutdown.

Duration of

2 minutes

2, 5, 7, 10, 12, 15, 18,

The low battery warning beeps

Low Battery Warning.

PowerChute

20 minutes

are continuous when two

software provides

minutes of run time remain.

automatic,

Change the warning interval

unattended

default to a higher setting if the

shutdown when

operating system requires a

approximately 2

longer interval for shutdown.

minutes of battery

operated runtime

remains.

Synchronized Turn-on

0 seconds

0, 20, 60, 120, 240, 480,

The UPS will wait the specified

Delay

720, 960 seconds

time after the return of utility

power before turn-on(to avoid

branch circuit overload).

High Bypass Point

+10% of

+5%, +10%, +15%,

Maximum voltage that the UPS

output voltage

+20%

will pass to connected

setting

equipment during internal

bypass operation.

Next >= Page 1 =12